Single-zone airflow
Inputs: Single mode: 252 ft² office, one person, Rp=5 CFM/person, Ra=0.06 CFM/ft² and Ez=1.0.
Calculation: People component = 5×1 = 5 CFM; area component = 0.06×252 = 15.12 CFM; Vbz = 20.12 CFM; Voz = 20.12/1.0.
Result: Vbz = 20.12 CFM; Voz = 20.12 CFM. These example inputs are supplied for arithmetic verification, not universal or current default rates.