Ventilation and air balance

Makeup Air Balance Calculator

Compare exhaust and replacement airstreams to estimate makeup airflow on the selected mass or volume basis.

Calculation inputs

This calculator runs in your browser and requires JavaScript.

An example is loaded automatically. Replace it with your project values; the result updates as you edit.

Use volume-flow balance when all streams share a compatible density basis, or use actual-density mass balance when they do not. Neither method predicts pressure.
Sum the exhausts simultaneously operating across the same defined boundary.
Count only intentional supply crossing that boundary; avoid double-counting recirculated air.
Use only a documented incoming transfer allowance; do not assume unlimited infiltration.
Zero requests neutral arithmetic flow balance. A positive value is a user-selected flow target, not a predicted pressure.

Download a PDF report

This creates a separate PDF from the current calculation.

Email is optional. If you provide one, it is saved only as a contact lead for this document; no email is sent and no marketing subscription is created. You can download directly without leaving an email.

Close this window or press Escape to continue without an email.

Privacy details

Loading example values…

Result

No result yet

Results appear automatically when inputs are valid.

Formula and source basis

Concepts behind this calculation

Calculate additional makeup airflow across a defined boundary using volume-flow balance or explicit actual-density mass balance.

Makeup air is a boundary accounting problem: identify simultaneous outgoing exhaust and the intentional incoming streams that can offset it. Volume balance is appropriate only when the streams have a compatible density basis. A selected surplus adds an explicit incoming-flow objective rather than predicting the pressure it will create.

When densities differ, each actual volume flow must first become a total-air mass flow. The remaining mass deficit is converted back to a required volume at the proposed makeup-air density. This separates conservation of mass from volume accounting; recirculation within the boundary and transfer already counted elsewhere must not be credited again.

How to use this calculator

  1. Choose Balance method after defining the boundary and simultaneous operation.
  2. For volume balance, enter Total scheduled exhaust, Existing intentional supply, Explicitly allowed incoming transfer, and Selected supply surplus target.
  3. For mass balance, document Density and mass-balance source, confirm Mass-balance basis confirmation, and enter each airflow with its matching total-air density, Makeup-air total density, and Selected mass-surplus target.
  4. Check that every credited stream crosses the boundary once.

Calculation method and applicability

Volume: Qmakeup=max(0,Qexhaust+target−Qsupply−Qtransfer). Mass: m=60×Q×ρ; Qmakeup=max(0,mexhaust+targetMass−msupply−mtransfer)/(60×ρmakeup).

Input definitions and units

Balance method
Use volume-flow balance when all streams share a compatible density basis, or use actual-density mass balance when they do not. Neither method predicts pressure. Choices: Volume-flow balance; Actual-density mass balance.
Total scheduled exhaust (CFM)
Sum the exhausts simultaneously operating across the same defined boundary. Applies to Balance method: Volume-flow balance.
Existing intentional supply (CFM)
Count only intentional supply crossing that boundary; avoid double-counting recirculated air. Applies to Balance method: Volume-flow balance.
Explicitly allowed incoming transfer (CFM)
Use only a documented incoming transfer allowance; do not assume unlimited infiltration. Applies to Balance method: Volume-flow balance.
Selected supply surplus target (CFM)
Zero requests neutral arithmetic flow balance. A positive value is a user-selected flow target, not a predicted pressure. Applies to Balance method: Volume-flow balance.
Density and mass-balance source
Identify the measurement, psychrometric state, design basis or other source for each total-air density and confirm that the streams cross the selected boundary once. This note is not authenticated. Applies to Balance method: Actual-density mass balance.
Mass-balance basis confirmation
Confirm stream direction, common boundary, total-air density basis and non-duplication of transfer air. The calculator checks arithmetic inputs only. Choices: Not confirmed; I confirmed the mass-balance basis. Applies to Balance method: Actual-density mass balance.
Exhaust airflow (ACFM at exhaust state)
Actual exhaust volume at the density entered below. Count only the simultaneous streams crossing this boundary. Applies to Balance method: Actual-density mass balance.
Exhaust total-air density (lbm/ft³)
Positive total-air density matching the exhaust airflow state; no universal default or lookup is applied. Applies to Balance method: Actual-density mass balance.
Intentional supply airflow (ACFM at supply state)
Actual intentional supply crossing the same boundary, at its entered density. Do not count recirculation twice. Applies to Balance method: Actual-density mass balance.
Supply total-air density (lbm/ft³)
Positive total-air density matching the supply airflow state. Applies to Balance method: Actual-density mass balance.
Allowed transfer airflow (ACFM at transfer state)
Actual incoming transfer at its entered density. Use only a documented transfer path and count it once. Applies to Balance method: Actual-density mass balance.
Transfer total-air density (lbm/ft³)
Positive total-air density matching the transfer airflow state. Applies to Balance method: Actual-density mass balance.
Makeup-air total density (lbm/ft³)
Positive total-air density at the proposed makeup-air state. The required CFM is reported at this density. Applies to Balance method: Actual-density mass balance.
Selected mass-surplus target (lbm/h)
User-selected positive incoming mass surplus target. Zero requests a neutral mass balance; this is not a pressure or code criterion. Applies to Balance method: Actual-density mass balance.

How to interpret the result

Read the requirement as an additional incoming stream on the selected boundary and density basis. Pressure control and conditioning that stream remain separate design tasks.

Worked examples

Volume-flow balance

Inputs: 600 CFM exhaust, 100 CFM intentional supply, 50 CFM allowed transfer, zero selected surplus.

Calculation: 600 − 100 − 50 = 450 CFM additional incoming air.

Result: 450 CFM required added makeup under the entered balance.

Actual-density mass balance

Inputs: Constructed actual-state case: 600 ACFM exhaust at 0.075 lbm/ft³; 100 ACFM supply at 0.070; 50 ACFM transfer at 0.080; proposed makeup density 0.065; selected mass surplus 0 lbm/h.

Calculation: Exhaust mass is 2,700 lbm/h; supply plus transfer is 660 lbm/h; deficit is 2,040 lbm/h. Divide by 60 × 0.065 to obtain the added makeup volume at the proposed makeup state.

Result: 523.077 CFM at makeup density; 2,040 lbm/h added makeup mass flow. This is a mass-balance result, not a pressure or code approval.

Assumptions and limits

  • Volume mode assumes compatible density basis. Mass mode conserves the user-supplied total-air mass flows with m = 60 × actual CFM × density; it does not infer density from temperature, humidity, altitude or weather.
  • The result is a boundary accounting calculation. It does not predict building pressure, envelope leakage, pressure coefficients, controls, combustion safety, hood capture, legal/code makeup-air fractions or equipment performance.
  • The schedule must use simultaneous streams crossing one defined boundary. The calculator cannot detect omitted paths, duplicate transfer air, unequal measurement conditions or an inapplicable density source.
  • No default density, infiltration credit, psychrometric lookup, outdoor-air conditioning load or mass-to-volume conversion outside the entered makeup density is applied.

FAQs

Does zero calculated makeup air mean the room will be neutral?

It means the entered streams satisfy the selected arithmetic target without added makeup flow. Room pressure still depends on leakage paths, resistances, controls, and omitted flows.

At which condition is the mass-method makeup CFM reported?

At Makeup-air total density. Changing that density changes the volume needed to supply the same missing mass, so it is not automatically exhaust-state or standard CFM.