Fans and energy

Fan Power Calculator

Use airflow, pressure, and efficiencies to estimate fan shaft power and electrical input.

Calculation inputs

This calculator runs in your browser and requires JavaScript.

An example is loaded automatically. Replace it with your project values; the result updates as you edit.

Use the airflow at the same operating point as the entered pressure and efficiencies.
Total pressure must use total fan efficiency; static pressure must use static fan efficiency.
This is fan total or fan static pressure from the selected basis, not an interchangeable TESP value.
Choose total or static efficiency to match the pressure selection; enter percent, not a decimal fraction.
Use efficiency at the intended motor loading; 100% represents an ideal boundary.
Include belt/drive losses as appropriate. Do not subtract the same loss twice.

Download a PDF report

This creates a separate PDF from the current calculation.

Email is optional. If you provide one, it is saved only as a contact lead for this document; no email is sent and no marketing subscription is created. You can download directly without leaving an email.

Close this window or press Escape to continue without an email.

Privacy details

Loading example values…

Result

No result yet

Results appear automatically when inputs are valid.

Formula and source basis

Concepts behind this calculation

Estimate air power, fan shaft BHP and electrical input kW from airflow, a matching pressure rise and actual efficiencies.

Air power measures the rate at which a fan supplies pressure energy to moving air. Operating airflow and matching pressure rise define that useful pressure-flow product. Fan efficiency connects air power to shaft power; motor and drive efficiencies then connect shaft power to electrical input. Each stage accounts for a different loss.

Pressure and efficiency must share the selected total or static basis. Mixing total pressure with static efficiency breaks the intended power balance. Efficiencies must also apply at the operating load: a peak catalog efficiency or motor rating does not automatically represent a part-load duty point. Enter percentages as shown by the fields.

How to use this calculator

  1. Select Pressure and fan-efficiency basis.
  2. Enter Operating airflow and Matching fan pressure rise at the same duty.
  3. Enter Matching fan efficiency, Motor efficiency, and Drive efficiency as percentages, then review each power stage.

Calculation method and applicability

P_air = Q × ΔP; P_shaft = P_air / η_fan; P_electric = P_shaft / (η_motor × η_drive)

Q = actual airflow; ΔP = pressure rise on the selected total/static basis; η = efficiency as a dimensionless fraction after conversion from the percentage fields. QΔP requires compatible physical units; the calculator converts CFM and in. w.g. before reporting shaft BHP and electrical kW.

Input definitions and units

Operating airflow (CFM)
Use the airflow at the same operating point as the entered pressure and efficiencies.
Pressure and fan-efficiency basis
Total pressure must use total fan efficiency; static pressure must use static fan efficiency. Choices: Fan total pressure and total efficiency; Fan static pressure and static efficiency.
Matching fan pressure rise (in. w.g.)
This is fan total or fan static pressure from the selected basis, not an interchangeable TESP value.
Matching fan efficiency (%)
Choose total or static efficiency to match the pressure selection; enter percent, not a decimal fraction.
Motor efficiency (%)
Use efficiency at the intended motor loading; 100% represents an ideal boundary.
Drive efficiency (%)
Include belt/drive losses as appropriate. Do not subtract the same loss twice.

How to interpret the result

Compare air, shaft, and electrical power to understand where the entered losses occur. W/CFM describes this duty point, while motor selection and electrical protection require additional information.

Worked examples

Worked example

Inputs: Approximately 2,118.88 CFM at 2.007315 in. w.g., equivalent to 1 m³/s at 500 Pa; fan efficiency 65%, motor 92%, drive 97%.

Calculation: Air power is 500 W. Divide by 0.65 for shaft power, then by 0.92 and 0.97 for electrical input.

Result: Approximately 1.032 BHP at the shaft and 0.862 kW electrical input.

Assumptions and limits

  • The selected pressure and fan efficiency must share a definition. Using total pressure with static efficiency overstates the required shaft power.
  • The estimate does not select a motor, wire, breaker or VFD, and it does not include a service factor or starting current.
  • Efficiency changes with fan operating point and motor loading. A nameplate maximum efficiency may not describe the actual duty.

FAQs

Which power result belongs in an energy-cost calculation?

Use electrical input kW with operating hours. Shaft BHP describes the mechanical fan load and omits motor and drive losses.

Should I include belt losses in both fan efficiency and drive efficiency?

Check the boundaries of the supplied efficiency data. Drive efficiency should account for losses that are not already included; counting the same loss twice inflates electrical demand.