Round duct: CFM from diameter and velocity
Inputs: 8 in round at 600 FPM.
Calculation: Area π(8/12)²/4 multiplied by 600 FPM.
Result: 209.4 CFM.
Airflow and velocity
Enter duct dimensions and CFM or air speed to solve for airflow, velocity, or capacity.
Check airflow, average velocity, a selected velocity limit, rectangular area change or aspect ratio from the existing duct dimensions.
Airflow is the volume crossing a duct section each minute. Multiplying clear area by an area-average velocity gives volume flow; a centerline reading can overstate that average when the velocity profile is uneven.
A velocity-limit check compares geometry with a selected design criterion. Changing cross-sectional area at unchanged CFM changes velocity, while an aspect-ratio check describes shape rather than pressure performance.
Q = V·A; V = Q/A; round A = π(D/12)²/4; rectangular A = WH/144
Q = volume flow (CFM); V = average velocity (FPM); A = clear area (ft²). D, W and H are inside dimensions in inches, converted by the displayed 12 or 144 divisor.
Read CFM as operating airflow only when velocity is measured and representative. A selected velocity cap produces theoretical geometric capacity; aspect and velocity flags apply only to the entered limits.
Inputs: 8 in round at 600 FPM.
Calculation: Area π(8/12)²/4 multiplied by 600 FPM.
Result: 209.4 CFM.
Inputs: 12 × 8 in at 600 FPM.
Calculation: Area 12×8/144 ft² multiplied by 600 FPM.
Result: 400 CFM.
Inputs: 400 CFM through a 10 in round duct.
Calculation: Divide flow by the clear round area.
Result: 733.4 FPM average velocity.
Inputs: 400 CFM through a 12 × 8 in rectangular duct.
Calculation: 400/(12×8/144).
Result: 600 FPM average velocity.
Inputs: 400 CFM, 10 in round duct, selected 700 FPM limit.
Calculation: Geometry gives about 733.4 FPM.
Result: Above the selected limit; this is not a code verdict.
Inputs: 400 CFM through 12×8 in then 8×8 in.
Calculation: Compute clear area and average velocity at both sections.
Result: 600 FPM → 900 FPM; area ratio 0.667.
Inputs: 24 × 6 in rectangle; selected limit 4:1.
Calculation: Width divided by height is 4:1.
Result: At the selected limit.
At the same imposed airflow it lowers average velocity. Actual operating airflow also depends on fan performance and system resistance, which this section check does not solve.
Use the clear inside opening after liner and obstructions. Outside sheet dimensions overstate the air passage and therefore overstate CFM calculated from velocity.