Leakage and balancing

Measured airflow balancing: compare, adjust, and remeasure

Use a complete simultaneous terminal schedule and explicitly selected criteria to separate design-band checks, group totals, and proportional balancing references.

Balancing starts with a valid measurement schedule

A balancing comparison is only meaningful when design and measured airflow use compatible references, the readings describe one stated operating condition, and every terminal belongs to an independently established balancing group. The workbench does not infer group membership from room names, correct density, or predict what a damper adjustment will do.

The terminal schedule mode reports several separate questions: whether each terminal lies within the selected design band, whether each group total lies within its selected total band, and whether the group’s terminal ratios are close to the lowest measured/design ratio. The retained supply/return mode only compares two total flows at one stated boundary.

A balancing schedule groups terminals with design and measured CFM. Each terminal ratio is compared with the selected design band, the lowest group ratio becomes the index, and proportional references are calculated without predicting a damper adjustment.
Design acceptance, group total, and proportional index checks answer different balancing questions.
The workbench outputs and their meanings.
CheckCalculationInterpretation
Terminal design bandMeasured CFM ÷ design CFMWhether an individual terminal is within selected lower/upper bounds
Group total bandGroup measured total ÷ group design totalWhether the group total is within its separate selected tolerance
Group indexLowest terminal ratio in that groupThe lowest measured/design ratio; all ties are retained
Proportional referenceTerminal design CFM × group indexA fixed-snapshot comparison reference, not a predicted adjusted flow
Proportional spread100 × (ratio/index − 1)Relative spread above the lowest ratio

Enter the schedule and selected criteria

Choose the terminal schedule mode, confirm the measurement and design reference basis, and enter one row per actual terminal: unique ID, independently established group ID, positive design CFM, and nonnegative measured CFM. Enter the selected design shortfall and excess allowances, group-total tolerance, and proportional-spread allowance as percentages. These are procedure inputs, not universal TAB tolerances.

Use the total supply/return mode only when supply and return CFM share a compatible boundary and operating condition. A difference can result from outdoor air, exhaust, transfer, leakage, or measurement boundaries; the simple comparison does not predict room pressure or prove a complete mass balance.

Run the calculation before deciding what to adjust. The output retains all lowest-ratio ties and labels proportional excess, but it does not issue damper commands, select fan speed, infer pressure loss, or estimate post-adjustment readings. Adjust under the governing field procedure and remeasure the same schedule.

Preparation checks before comparing readings.
InputRequirementDo not infer
Design flowSource and state documented for each terminalA design value from another operating condition
Measured flowInstrument/procedure correction and same stated conditionA missing terminal or zero from an omitted reading
Group IDActual balancing group established from topology/procedureAutomatic grouping by room or supply/return label
CriteriaSelected lower/upper, group-total, and spread limitsA universal tolerance from the calculator

Independent terminal and group example

Use Group 1 design flows 200, 400, and 400 CFM with measured flows 160, 400, and 390 CFM. The ratios are 0.80, 1.00, and 0.975. With a selected ±10% design band, terminal 1 is outside while terminals 2 and 3 are inside. The group design total is 1,000 CFM and the measured total is 950 CFM, so the group total is 95.0%, exactly at the lower edge of a selected ±5% group-total band.

The group index is 0.80. Proportional references are design × 0.80: 160, 320, and 320 CFM. The measured-minus-reference differences are 0, 80, and 70 CFM. Group 1 proportional spread is 100 × (1.00/0.80 − 1) = 25.0%, so it fails a selected 5% spread even though two terminals meet the design band and the group total sits at its selected lower edge.

Group 2 has design 300/300 and measured 330/330 CFM. Both ratios are 1.10, both terminals tie as index terminals, the group total is 110% and fails the selected ±5% group-total band, while its proportional spread is 0%. This shows why a good proportional match does not prove the group total is acceptable.

Group 1 index = min(0.80, 1.00, 0.975) = 0.80 Terminal 2 proportional reference = 400 × 0.80 = 320 CFM Terminal 3 proportional reference = 400 × 0.80 = 320 CFM Group 1 spread = (1.00/0.80 − 1) × 100 = 25.0%

Independent arithmetic compared with the calculator result.
ResultIndependent valueCalculator display
Group 1 measured total160 + 400 + 390 = 950 CFM950 CFM
Group 1 total percent950/1,000 × 100 = 95.0%95.0%
Group 1 index0.800.80
Terminal 2 proportional reference400 × 0.80 = 320 CFM320 CFM
Group 1 largest proportional excess25.0%25.0%
Group 2 proportional spread1.10/1.10 − 1 = 0%0%

Use the result to plan the next measurement

Start with the governing selected criterion and the terminal/group that fails it. Check the measurement setup, instrument correction, damper/control state, branch path, and pressure conditions before changing hardware. A terminal below design may be caused by a restriction or reference error; a terminal above design may affect other branches after adjustment.

After an adjustment, repeat the complete affected schedule under the same stated condition. Recalculate the ratios, group totals, index ties, and spread. Do not carry old proportional references forward as a target instruction, because changing one terminal changes the distribution available to the others.

How to read common outcomes.
OutcomeWhat it saysWhat it does not say
Terminal outside design bandOne measured/design ratio fails the selected rangeThe cause or required damper movement
Group total failsThe group sum fails its selected total criterionThat every terminal in the group is wrong in the same way
Spread failsTerminal ratios are too far apart relative to the lowest ratioThe group needs a specific adjustment sequence
All checks passEntered snapshot meets selected arithmetic criteriaFinal commissioning, pressure, noise, or code approval

FAQs

Why can a group total pass while a terminal fails? A high terminal and a low terminal can offset in the sum. Review individual ratios and the group total separately.

Why can proportional spread pass while the group is above design? If every terminal is 110% of design, their ratios are equal and spread is zero, but the group total is still 110%.

Does the index terminal tell me which damper to close? No. It identifies the lowest measured/design ratio in the supplied snapshot. Adjustment order and control response require the actual procedure and field evidence.

Conclusion and limits

Collect a complete simultaneous schedule, establish groups and compatible flow references, then read terminal design bands, group totals, and proportional spread as separate checks. After any adjustment, repeat the measurements under the same condition.

The workbench is a transparent arithmetic aid for the supplied snapshot. It does not calculate density corrections, pressure, leakage, damper commands, fan response, ventilation minimums, or final commissioning acceptance.

Related calculators