CFM from room volume and ACH
Inputs: 1,200 ft³ room volume at selected 4 ACH.
Calculation: 1,200×4/60.
Result: 80 CFM nominal airflow.
Ventilation and air balance
Enter room volume and an air-change target to calculate the corresponding airflow.
Convert a selected room air-change rate and volume into an equivalent airflow, or derive ACH from known CFM.
Air changes per hour is volume flow normalized by room air volume. It counts equivalent room volumes, not the number of times every parcel is replaced.
Supply ACH, exhaust ACH and outdoor-air ACH describe different streams. A recirculating supply volume cannot be relabeled as outdoor ventilation without knowing its outdoor fraction.
CFM = room ft³ × ACH ÷ 60; ACH = 60 × CFM ÷ room ft³
CFM = volume flow in ft³/min; room volume is ft³; ACH = equivalent room volumes per hour. The factor 60 converts between minutes and hours.
The result is a volume-normalized flow relationship. Retain the stream identity and room-volume boundary when comparing it with a project ACH target.
Inputs: 1,200 ft³ room volume at selected 4 ACH.
Calculation: 1,200×4/60.
Result: 80 CFM nominal airflow.
Inputs: 1,200 ft³ volume with 80 CFM.
Calculation: 60×80/1,200.
Result: 4 ACH.
It means the equivalent of one room volume flows in ten minutes. Mixing, short circuits and recirculation determine how contaminants actually clear.
Enter an independently selected project or applicable method requirement. This geometry conversion does not choose a room-use requirement or establish air quality.