Ventilation and air balance

Outdoor Air Load Calculator

Compare outdoor-air states and flows with target conditions to calculate cooling, heating, and moisture duties.

Calculation inputs

This calculator runs in your browser and requires JavaScript.

An example is loaded automatically. Replace it with your project values; the result updates as you edit.

Required: record location/station, data source/edition, design percentile, condition pairing and row meanings. For measured cases record sensor/date/basis. No station or percentile is inferred.
Use one measured/design actual flow for all weather alternatives, or enter the actual delivered ventilation flow separately for each operating state. This is not an annual energy schedule.
Used in shared-flow mode only. Actual volume at each entered outdoor state, not SCFM or target-room CFM; dry-air mass changes with state-specific specific volume.
Same site pressure for outdoor and target states. Do not enter gauge/static duct pressure. No station elevation or pressure is inferred.
The desired ventilation-air state, which may be room-equivalent or a supply condition. Not automatically a coil leaving condition.
Use RH matching target dry-bulb and pressure. Source convention uses saturation over ice below the triple point; check subfreezing weather RH conventions.
Air-stream duty compares air enthalpies. Liquid-drain correction additionally subtracts discharged water enthalpy; use only for above-freezing dehumidification, not humidification.
Shared-flow mode: enter 1–20 rows of temperature and RH separated by comma; the same ACFM applies to every row. Document case order and use coincident pairs from each chosen design category; do not combine independent maxima.

Download a PDF report

This creates a separate PDF from the current calculation.

Email is optional. If you provide one, it is saved only as a contact lead for this document; no email is sent and no marketing subscription is created. You can download directly without leaving an email.

Close this window or press Escape to continue without an email.

Privacy details

Loading example values…

Result

No result yet

Results appear automatically when inputs are valid.

Formula and source basis

Concepts behind this calculation

Compare sensible, moisture and total outdoor-air treatment duty across entered weather states using either one shared actual airflow or a separate airflow for each state.

Outdoor-air conditioning load compares the entering outdoor state with a selected target air state. Actual outdoor CFM is converted to dry-air mass using the specific volume of each outdoor state. Humidity ratio and enthalpy then describe the moisture and energy changes; identical actual CFM across cases need not carry identical dry-air mass.

Sensible and latent components describe the stated process convention, while their selected total governs the air-stream balance. Opposing temperature and moisture demands can cancel in a small net total. Liquid-drain correction additionally accounts for discharged water energy and is restricted to compatible above-freezing water removal. Alternative weather cases are separate possibilities, not simultaneous loads.

How to use this calculator

  1. Document Weather/design condition reference and select Outdoor airflow across cases.
  2. Enter Absolute barometric pressure, Target air dry-bulb, and Target air relative humidity.
  3. Use Outdoor actual airflow per scenario with Outdoor design-state rows, or complete Per-case airflow and outdoor-state rows with coincident conditions.
  4. Select Energy convention and, if applicable, supply Drained liquid-water specific enthalpy; inspect each row’s signed components before comparing maxima.

Calculation method and applicability

pw=RH×pws(T); W=0.621945×pw/(p−pw); h=0.240T+W(1061+0.444T); v=0.370486(T+459.67)(1+1.607858W)/p[psia]; mda=60Qout,actual/v; Qair=mda(hout−htarget); Qs=mda(0.240+0.444Wout)(Tout−Ttarget); optional Qdrain=mda(Wout−Wtarget)hwater; selected Qt=Qair−Qdrain; Qlatent=Qt−Qs.

p/pw = total/vapor pressure (psia); W = humidity ratio (lb water/lb dry air); h = enthalpy (BTU/lb dry air); v = specific volume (ft³/lb dry air); mda = dry-air mass flow (lb/h). Thermal Q terms are BTU/h, whereas Qout,actual is outdoor ACFM.

Input definitions and units

Weather/design condition reference
Required: record location/station, data source/edition, design percentile, condition pairing and row meanings. For measured cases record sensor/date/basis. No station or percentile is inferred.
Outdoor airflow across cases
Use one measured/design actual flow for all weather alternatives, or enter the actual delivered ventilation flow separately for each operating state. This is not an annual energy schedule. Choices: One shared airflow; Airflow varies by case.
Outdoor actual airflow per scenario (ACFM)
Used in shared-flow mode only. Actual volume at each entered outdoor state, not SCFM or target-room CFM; dry-air mass changes with state-specific specific volume. Applies to Outdoor airflow across cases: One shared airflow.
Absolute barometric pressure (psia)
Same site pressure for outdoor and target states. Do not enter gauge/static duct pressure. No station elevation or pressure is inferred.
Target air dry-bulb (°F)
The desired ventilation-air state, which may be room-equivalent or a supply condition. Not automatically a coil leaving condition.
Target air relative humidity (%)
Use RH matching target dry-bulb and pressure. Source convention uses saturation over ice below the triple point; check subfreezing weather RH conventions.
Energy convention
Air-stream duty compares air enthalpies. Liquid-drain correction additionally subtracts discharged water enthalpy; use only for above-freezing dehumidification, not humidification. Choices: Air-stream enthalpy duty; Include liquid condensate drainage.
Drained liquid-water specific enthalpy (BTU/lb water)
Use a liquid-water property at the drain temperature on the same ASHRAE enthalpy reference (approximately zero at 32°F). 18.07 is the Handbook example at 50°F, not a default for every target. Applies to Energy convention: Include liquid condensate drainage.
Outdoor design-state rows (°F, RH %)
Shared-flow mode: enter 1–20 rows of temperature and RH separated by comma; the same ACFM applies to every row. Document case order and use coincident pairs from each chosen design category; do not combine independent maxima. Applies to Outdoor airflow across cases: One shared airflow.
Per-case airflow and outdoor-state rows (ACFM, °F, RH %)
Per-state schedule mode: enter 1–20 rows of actual outdoor ACFM, dry-bulb temperature and RH. Enter zero ACFM for an explicit off case. These are discrete operating scenarios, not annual energy bins. Applies to Outdoor airflow across cases: Airflow varies by case.

How to interpret the result

Positive removal represents cooling/dehumidification duty; negative total represents heating/humidification demand. Case maxima apply only to supplied alternatives and do not constitute a whole-building equipment load.

Worked examples

One shared airflow

Inputs: Shared-flow mode: 1,000 outdoor ACFM at 14.696 psia; target 75°F / 50% RH. Outdoor rows: 95°F / 60%, 82°F / 90%, 100°F / 40%. All conditions are constructed examples, not a weather-station dataset.

Calculation: For each state, calculate dry-air mass from the shared 1,000 ACFM and that state's specific volume; compute total enthalpy removal and sensible load. Latent is the selected total balance minus sensible.

Result: Maximum cooling removal 76,099.493 BTU/h in Case 1. Separate sensible/latent maxima must not be added.

Airflow varies by case

Inputs: Per-state airflow mode: 1,000 ACFM at 95°F / 60% RH; 500 ACFM at 82°F / 90% RH; 2,000 ACFM at 100°F / 40% RH; target 75°F / 50% RH at 14.696 psia. Constructed cases only.

Calculation: Each row uses its own ACFM and outdoor specific volume to calculate dry-air mass. Total removal scales with that row's mass flow; rows are evaluated independently.

Result: Case 1: 76,099.493 BTU/h; Case 2: 31,826.375 BTU/h; Case 3: 117,219.292 BTU/h. The controlling cooling case is Case 3.

Assumptions and limits

  • Calculates outdoor ventilation air only. It does not determine required ventilation flow, whole-building loads, duct heat gain, supply-fan heat, mixing, reheat, equipment capacity, recovery efficiency or code compliance.
  • Dry-air mass is calculated separately for each state as 60 ×ACFM/v, not an assumed4.5×CFM. Shared-flow mode applies one entered actual CFM to every state; per-state mode uses the corresponding row's actual CFM. Standard-volume, room-volume or fixed-mass input is not automatically converted.
  • Named psychrometric basis: ASHRAE 2017 perfect-gas humidity ratio, enthalpy and volume relations with SI Hyland-Wexler saturation coefficients and a triple-point branch. These engineering approximations are not real-gas IAPWS properties or a complete psychrometric tool.
  • Supported temperatures −40 to 140°F; RH 0–100%. Below the water triple point, the saturation relation is over ice. Many weather RH records use a liquid-water reference below freezing; convert such data before entry rather than mixing conventions. Vapor partial pressure must remain below total pressure.
  • Sensible/latent separation follows the stated temperature change at fixed OUTDOOR humidity ratio, then moisture change at target dry-bulb. Another process convention can allocate components differently; their selected total balance remains the governing result.
  • Positive removal means cooling/dehumidification; negative means heating/humidification demand. A net enthalpy near zero can still require separate sensible cooling/heating and moisture treatment. Air-stream duty excludes condensate and water/steam-side enthalpy.
  • Liquid-drain mode subtracts discharged liquid enthalpy and is restricted to above-freezing water removal for every scenario. It does not model frosting or a humidifier. Drain enthalpy must match its actual temperature and reference; do not use18.07 universally.
  • No weather database, station autofill or design-percentile selection is embedded. The reference text is user supplied and not authenticated. Use documented coincident pairs, including appropriate dehumidification/enthalpy conditions, not only the hottest dry bulb.
  • Case maxima are across alternatives, not simultaneous loads. Per-state mode evaluates discrete rows only and does not integrate runtime, annual energy or control transitions. Approximate property equations and rounded source chart benchmarks have stated verification limits.

FAQs

Can I add the largest sensible and latent loads from different rows?

That creates a case not represented by the entered conditions. Review each complete coincident state and carry the controlling scenario into further design.

Does a near-zero total mean the outdoor air needs no treatment?

No. Sensible cooling can offset a moisture-related heating contribution, or the reverse. Inspect the signed components and required humidity change even when net enthalpy duty is small.

Sources

  • ASHRAE 2017 Fundamentals, IP Chapter 1: PsychrometricsOriginal Equations 20, 25, 26, 30, 41, and 43 directly inspected. Example 3 supplies a rounded cooling/dehumidification case and liquid-drain energy balance; source chart rounding is kept distinct from the continuous-equation calculation.
  • ASHRAE 2017 Fundamentals, SI Chapter 1Hyland-Wexler saturation coefficients directly inspected in Batch14; reused here. Water/ice branch convention documented in the method.
  • CaptiveAire: Outdoor Air Load CalculatorDirect same-intent peer: distinguishes cooling, dehumidification and enthalpy design scenarios. Its weather dataset and fixed-coefficient formulas are not copied; this page requires your own traceable design states.

Related calculators