Calculate measured TESP
Inputs: Daikin DD96TN installation-instruction example: supply static +0.3 in. w.g. and return static −0.1 in. w.g.; measurements are taken at the manual's shown equipment test openings.
Calculation: TESP = +0.3 − (−0.1) = 0.4 in. w.g.
Result: 0.4 in. w.g. TESP. The manual's example verifies the arithmetic; on a job, use the actual equipment's measurement boundary and operating condition.