Duct thermal and materials

Duct Heat Loss and Outlet Temperature Calculator

Enter duct geometry, insulation, and air conditions to estimate heat transfer and outlet temperature.

Calculation inputs

This calculator runs in your browser and requires JavaScript.

An example is loaded automatically. Replace it with your project values; the result updates as you edit.

Retain the original standard-air single-run screen, or use explicit inlet mass flow and overall U values for an ordered section chain.
Air temperature at the start of the run or section chain. Negative Fahrenheit is valid above absolute zero. Use the chosen method’s air-property and phase assumptions.
Use an approximately constant ambient temperature for this run, not a weather extreme applied to every space.
Screening uses the original standard-air basis. Ordered mode requires actual inlet volume flow at the same state as the supplied total-air density; SCFM is not interchangeable. The chain conserves mass flow, not local CFM.
Zero length is a valid boundary and returns the inlet temperature.
For a rectangular duct use 2 × (outside width + outside height); for round use π × outside diameter.
Enter installed insulation thermal resistance. Zero represents no added insulation; the model still includes 0.85 combined film resistance.

Download a PDF report

This creates a separate PDF from the current calculation.

Email is optional. If you provide one, it is saved only as a contact lead for this document; no email is sent and no marketing subscription is created. You can download directly without leaving an email.

Close this window or press Escape to continue without an email.

Privacy details

Loading example values…

Result

No result yet

Results appear automatically when inputs are valid.

Formula and source basis

Concepts behind this calculation

Estimate duct heat loss or gain and outlet air temperature using the original standard-air screening model or an ordered section model with explicit air properties and overall U-values.

Duct air gradually approaches the temperature of its surroundings as heat crosses the duct assembly. The exponential temperature response reflects a shrinking driving temperature difference along the run. Greater heat-transfer area or conductance increases the approach; greater air heat-capacity flow reduces the temperature change for the same exposure.

The single-run screen uses fixed standard-air properties and an added film resistance with the entered insulation R-value. Ordered sections instead use actual inlet flow, matching total-air density, compatible specific heat, and an independently established overall U for each section. The outlet of one section becomes the inlet of the next, so a cold space followed by a warm space cannot be replaced casually by one average ambient temperature.

How to use this calculator

  1. Select Thermal calculation method and enter Inlet air temperature and Duct airflow.
  2. For screening, enter Average surrounding temperature, Run length, Outside duct perimeter, and Insulation R-value.
  3. For ordered sections, supply Inlet total-air density and Compatible total-air specific heat, document the U-area reference, and confirm Ordered sensible-model basis.
  4. Enter Sections in airflow order and review the section trace before the net result.

Calculation method and applicability

U = 1 / (R_insulation + 0.85); A = perimeter × length; T_out = T_ambient + (T_in − T_ambient) × exp[−UA / (1.08 × CFM)] Ordered model: m=60×Qinlet×ρinlet; C=m×cp; Ai=Pi[in]/12×Li[ft]; Ti,out=Ta,i+(Ti,in−Ta,i)exp(−UiAi/C); qi=C(Ti,in−Ti,out); Ti+1,in=Ti,out. Net=Σqi; gross loss=Σmax(0,qi); gross gain=Σmax(0,−qi).

U = overall conductance (BTU/(h·ft²·°F)); A = heat-transfer area (ft²); m = air mass flow (lbm/h); C = thermal capacity rate (BTU/(h·°F)); q = heat transfer (BTU/h). T is °F. Section perimeter P is entered in inches and length L in feet.

Input definitions and units

Thermal calculation method
Retain the original standard-air single-run screen, or use explicit inlet mass flow and overall U values for an ordered section chain. Choices: Standard-air single-run screening; Ordered sections with explicit properties and U.
Inlet air temperature (°F)
Air temperature at the start of the run or section chain. Negative Fahrenheit is valid above absolute zero. Use the chosen method’s air-property and phase assumptions.
Average surrounding temperature (°F)
Use an approximately constant ambient temperature for this run, not a weather extreme applied to every space. Applies to Thermal calculation method: Standard-air single-run screening.
Duct airflow (CFM)
Screening uses the original standard-air basis. Ordered mode requires actual inlet volume flow at the same state as the supplied total-air density; SCFM is not interchangeable. The chain conserves mass flow, not local CFM.
Run length (ft)
Zero length is a valid boundary and returns the inlet temperature. Applies to Thermal calculation method: Standard-air single-run screening.
Outside duct perimeter (in)
For a rectangular duct use 2 × (outside width + outside height); for round use π × outside diameter. Applies to Thermal calculation method: Standard-air single-run screening.
Insulation R-value (h·ft²·°F/BTU)
Enter installed insulation thermal resistance. Zero represents no added insulation; the model still includes 0.85 combined film resistance. Applies to Thermal calculation method: Standard-air single-run screening.
Inlet total-air density (lbm/ft³)
Actual inlet total-air density in lbm/ft³, paired with inlet ACFM. Supply an independently established value; no altitude, weather or standard-air default. Applies to Thermal calculation method: Ordered sections with explicit properties and U.
Compatible total-air specific heat (BTU/(lbm·°F))
One applicable constant specific heat per pound of the same total-air mass basis as density, valid over all section temperatures. Do not pair dry-air-basis cp with moist total-air density. Applies to Thermal calculation method: Ordered sections with explicit properties and U.
Section order,properties and U-area reference
Identify the actual air-property basis, ordered locations, overall U sources and matching area/perimeter reference. Confirm U includes applicable films, wall and insulation and applies over the modeled temperatures. This reference is not authenticated. Applies to Thermal calculation method: Ordered sections with explicit properties and U.
Ordered sensible-model basis
Confirm one stream without leakage, compatible constant mass flow and cp, a single gas phase, steady sections and independently established overall U on the entered perimeter basis. Choices: Not established; Section and property basis documented. Applies to Thermal calculation method: Ordered sections with explicit properties and U.
Sections in airflow order (length ft, perimeter in, U BTU/(h·ft²·°F), surroundings °F)
Enter 1–100 numeric rows in airflow order, without branches, mixing or fan heat. Overall U includes all applicable resistances on the entered area basis; no fixed film resistance is added. U=0 is an ideal adiabatic boundary; length=0 is valid; perimeter must be positive. Applies to Thermal calculation method: Ordered sections with explicit properties and U.

How to interpret the result

Positive transfer is heat leaving the air; negative transfer is heat entering it. Inspect section temperatures and both gross totals, because a modest final temperature change can hide substantial intermediate transfer.

Worked examples

Standard-air single-run screening

Inputs: 120°F inlet, 75°F ambient, 500 CFM, 50 ft long, 48 in perimeter and R-6 insulation.

Calculation: Area = 200 ft². U = 1/6.85. The standard-air heat-capacity rate is 1.08 × 500 = 540 BTU/(h·°F).

Result: Outlet temperature 117.632°F; about 1,278.981 BTU/h leaves the duct air.

Ordered sections with explicit properties and U

Inputs: Constructed 500 inlet ACFM at 120°F, total-air density 0.06 lbm/ft³ and cp 0.24 BTU/(lbm·°F). Section 1: 50 ft, 48 in perimeter, overall U 0.2, surroundings 60°F. Section 2: 25 ft, 48 in perimeter, U 0.4, surroundings 140°F.

Calculation: Mass flow=60×500×0.06=1,800 lbm/h; C=432 BTU/(h·°F). Each section has UA=40. The first outlet is 114.693888°F; the second is 116.931839°F. Section 1 loses 2,292.240309 BTU/h; section 2 gains 966.794826 BTU/h. Net heat leaving air is 1,325.445482 BTU/h.

Result: 116.932°F outlet; 1,325.445 BTU/h net leaving air. Gross loss of 2,292.240 BTU/h and gross gain of 966.795 BTU/h remain separate.

Assumptions and limits

  • The original screening mode assumes one-dimensional steady heat transfer, constant U and specific heat, combined inside/outside film resistance of 0.85 h·ft²·°F/BTU, and no leakage.
  • The original screening mode fixes density at 0.075 lb/ft³ and cp at 0.24 BTU/(lb·°F). Select ordered mode when using independently established actual inlet mass flow, compatible constant cp and overall U.
  • Insulation compression, moisture, thermal bridges, vapor-control detailing and surface condensation are not evaluated. This does not certify an insulation thickness or code minimum.
  • Ordered mode conserves mass flow from actual inlet CFM and matching total-air density, using one compatible constant total-air cp. Local CFM is not held constant or predicted. It handles 1–100 sequential sections without branches or mixing.
  • Ordered mode requires independently established overall U on the entered perimeter/area basis, including applicable films, wall and insulation. It adds no fixed film resistance and does not derive U from material data.
  • Both methods are steady sensible-only approximations. Moisture phase changes, latent loads, leakage, thermal storage, separate solar/radiant boundary solutions and fan heat are not modeled. Confirm a single gas phase and valid fixed properties; no saturation or condensation check is performed.
  • For very small NTU, the outlet temperature can round to the inlet while the stable energy result remains nonzero. The heat balance uses unrounded transfer; no physical measurement precision is implied.

FAQs

Why can gross heat loss exceed the net heat loss?

Some sections can remove heat while others add it back. Net transfer subtracts those opposing effects; gross loss and gross gain preserve the separate exposures.

Should I enter insulation conductance alone as overall U?

No. Ordered-section U must include the applicable films, wall, and insulation on the same area basis as the entered perimeter. That method does not add the screening film resistance for you.

Sources