Flat — check installed thickness
Inputs: Ambient 85°F at 70% RH; bulk duct air 55°F; k=0.25 BTU·in/(h·ft²·°F), inside h=4, combined outside h=1.2 BTU/(h·ft²·°F), wall 0.02 in at k=26 BTU/(h·ft·°F); target allowance 2°F. One-dimensional flat wall; excludes corners. Installed insulation 1 in.
Calculation: Invert the named ASHRAE 2017 saturation relation for dew point 74.115050°F, giving target 76.115050°F. Sum inside-film, wall, insulation and outside-film resistances, preserving cylindrical areas for round ducts.
Result: Outer surface at 1 in: 80.082029°F; conditional minimum for the target: 0.432587316 in. These use illustrative constant properties and do not certify installation or code compliance.