Blower Table Airflow Calculator
Inputs: Lennox 011Q3-105 historical blower table: measured TESP +0.35 in. w.g.; four tap curves use .30/.40 in. w.g. points. The OEM note states airflow was measured external to the furnace with the air filter in place.
Calculation: For tap 1: 1495 + (.35−.30)/(.40−.30)×(1450−1495) = 1472.5 CFM. Apply the same local interpolation to taps 2–4; no values outside the table span are estimated.
Result: Tap 1: 1472.5 CFM; tap 2: 1237.5 CFM; tap 3: 932.5 CFM; tap 4: 757.5 CFM at 0.35 in. w.g. Historical model-specific reference case only.