Estimate free and gross grille area
Inputs: 400 CFM, selected 500 FPM and actual product free-area ratio 0.5.
Calculation: Free area 0.8 ft²; gross area 0.8/0.5.
Result: 0.8 ft² free and 1.6 ft² gross area.
Duct component selection
Use airflow, opening dimensions, and free-area data to check grille size and velocity.
Estimate grille free/gross area, compare terminal opening geometry, or screen one exact product pressure curve against selected airflow limits.
A terminal has several meaningful areas: gross face, free opening, core and neck. Velocity must use the exact area definition attached to the product performance or selected criterion.
A geometric opening estimate cannot predict a product’s pressure curve. A curve check needs the exact model, size and configuration, with pressure points on a common rating basis.
A_free = CFM / face velocity; A_gross = A_free/free-area ratio; V = CFM/A_clear; Δp(Q) is exact at supplied points and piecewise-linear only between adjacent points.
A_free and A_gross = free and gross face areas (ft²); V = velocity on the stated clear/reference area (FPM); Q = volume flow (CFM); Δp = positive pressure-drop magnitude (in. w.g.). The free-area ratio is a fraction, not a percentage.
Interpret area sizing as preliminary geometry. In product-curve mode retain the area basis, source bracket and separate pressure and velocity margins; a supported point does not establish throw or room sound.
Inputs: 400 CFM, selected 500 FPM and actual product free-area ratio 0.5.
Calculation: Free area 0.8 ft²; gross area 0.8/0.5.
Result: 0.8 ft² free and 1.6 ft² gross area.
Inputs: 400 CFM at selected 500 FPM.
Calculation: 400/500.
Result: 0.8 ft² required free area.
Inputs: 400 CFM, duct area 0.667 ft² and terminal clear area 0.8 ft².
Calculation: Divide flow by each area.
Result: About 599.7 FPM duct and 500 FPM terminal.
Inputs: 8 in connecting duct and 7 in opening equivalent diameter.
Calculation: Compare only the entered geometry.
Result: Check opening size; this does not certify a product.
Inputs: Titus 350R/350F/350R-SS nominal 6×6 in source point: 114 CFM, 0.19 ft² core area, 0.073 in. w.g. negative static-pressure magnitude; user limits 0.08 in. w.g. and 650 FPM.
Calculation: Source table reports 600 FPM core velocity, 0.022 in. w.g. velocity pressure and 0.073 in. w.g. negative static pressure magnitude. CFM ÷ 0.19 ft² = 600 FPM; both entered limits are met at this exact point.
Result: Within entered limits: 0.073 in. w.g. at 114 CFM, 600 FPM at core area. Historic catalog point only; not a current product or installed-performance certification.
It can convert free area to gross area for a preliminary opening estimate. Blade geometry, flow direction and product construction still require a matching pressure curve.
The product may rate gross face, core, free or neck area. The connecting duct uses its own clear area; equal CFM does not imply equal velocity at both planes.