Series and Parallel Fan Curve Calculator

Combine matched fan curves in series or parallel and compare their resulting operating points.

Calculation inputs

This calculator runs in your browser and requires JavaScript.

An example is loaded automatically. Replace it with your project values; the result updates as you edit.

Whole-number count from 1 to 100. All entered fans are assumed to have the same curve at compatible speed/density.
Parallel adds flow at equal pressure; series adds pressure at equal flow.
One flow and matching fan pressure per line, sorted by strictly increasing CFM. Use actual manufacturer/test data at the selected speed/density and a consistent total/static basis. Example is synthetic, not a real fan.
A known airflow used to define the system friction curve, not an assumed operating point.
Flow-dependent friction component only. Exclude the separate flow-independent term below.
Enter zero for a purely frictional closed air circuit. This is a system-curve constant, not fan static pressure or TESP.

Download a PDF report

This creates a separate PDF from the current calculation.

Email is optional. If you provide one, it is saved only as a contact lead for this document; no email is sent and no marketing subscription is created. You can download directly without leaving an email.

Close this window or press Escape to continue without an email.

Privacy details

Loading example values…

Result

No result yet

Results appear automatically when inputs are valid.

Formula and source basis

Concepts behind this calculation

Combine identical fan curves in parallel or series, then find their intersections with the actual system curve instead of multiplying a single duty-point airflow.

Identical fans in parallel contribute flow at a shared pressure, stretching the combined curve horizontally. Identical fans in series contribute pressure at a shared flow, stretching it vertically. These are combinations of fan curves, not promises to multiply the installed system airflow.

The combined curve must still intersect the same quadratic-plus-constant system model. Increased flow raises friction resistance, so added parallel fans generally do not produce a proportional flow increase. The ideal combination also omits installation interaction, failed-fan backflow, unequal performance, and sequencing effects that can change real results.

How to use this calculator

  1. Enter Identical fans and select Fan connection.
  2. Provide the single-fan Supplied fan curve at the applicable speed and density.
  3. Enter System reference airflow, Friction pressure at reference airflow, and Flow-independent pressure term, then inspect the combined operating candidates.

Calculation method and applicability

Parallel: add flows at equal pressure. Series: add pressures at equal flow. Intersect the combined fan curve with P_constant + kQ².

Q = combined airflow (CFM); pressure is in. w.g. The number of fans is a count. Series curves add pressure at common flow; parallel curves add flow at common pressure.

Input definitions and units

Identical fans (count)
Whole-number count from 1 to 100. All entered fans are assumed to have the same curve at compatible speed/density.
Fan connection
Parallel adds flow at equal pressure; series adds pressure at equal flow. Choices: Parallel — shared pressure; Series — shared airflow.
Supplied fan curve (CFM, in. w.g.)
One flow and matching fan pressure per line, sorted by strictly increasing CFM. Use actual manufacturer/test data at the selected speed/density and a consistent total/static basis. Example is synthetic, not a real fan.
System reference airflow (CFM)
A known airflow used to define the system friction curve, not an assumed operating point.
Friction pressure at reference airflow (in. w.g.)
Flow-dependent friction component only. Exclude the separate flow-independent term below.
Flow-independent pressure term (in. w.g.)
Enter zero for a purely frictional closed air circuit. This is a system-curve constant, not fan static pressure or TESP.

How to interpret the result

Read combined airflow and pressure at the system intersection, rather than multiplying a single-fan duty point. Multiple intersections still require separate stability and equipment review.

Worked examples

Worked example

Inputs: Two identical fans, each with synthetic points (0 CFM, 2 in. w.g.) and (2,000, 0), in parallel. System friction is 1 in. w.g. at 1,000 CFM, constant term zero.

Calculation: The combined parallel curve doubles flow at each pressure, but the system resistance rises with the square of total flow.

Result: About 1,186.141 CFM at 1.407 in. w.g.; not twice the single-fan 1,000 CFM operating point.

Assumptions and limits

  • Fan data are interpolated linearly only between supplied points. No extrapolation, manufacturer data download or invented fan curve is performed.
  • System resistance is modeled as a quadratic friction term plus a nonnegative flow-independent term. Real equipment, controls and flow regimes may differ.
  • Multiple intersections are all shown. Dynamic stability, stall, surge, transient behavior, noise and safe fan operating range need separate review.
  • All fan/system pressures must use compatible total/static definitions and air-density conditions. The synthetic example is not a real product selection.
  • This ideal combination excludes fan-to-fan interaction, inlet/outlet system effect, unequal fans, failed-fan backflow, control sequencing and actual installation losses.
  • More fans do not guarantee proportionally more system airflow. Series/parallel curve combination still requires the shared system intersection.

FAQs

Should I enter the combined curve in Supplied fan curve?

Enter the curve for one fan. The selected count and connection construct the ideal combined curve; entering an already combined curve would repeat that scaling.

Can I use this model for fans of different sizes?

No. Every entered fan is assumed to share the same curve at compatible speed and density. Unequal fans require a different combination analysis.