Actual ACFM to reference SCFM
Inputs: Constructed example: 1,000 ACFM at 95°F, 14.2 psia and 40% RH. User-defined reference: 70°F, 14.696 psia and 0% RH.
Calculation: ASHRAE perfect-gas moist-air properties give vactual = 14.8122278832 and vreference = 13.3529749333 ft³/lb dry air. Qreference = 1,000 × 13.3529749333 / 14.8122278832; dry-air flow = 60 × 1,000 / 14.8122278832.
Result: 901.483 SCFM at the explicitly entered reference state; dry-air mass flow is 4,050.707 lb dry air/h.