Worked example
Inputs: Historical McGill RSF-LV-L 31 p 12: 4 ft² face at +1250 FPM (5000 CFM), 36/60/84 in lengths; dynamic IL and generated noise use matching source rows. Candidate 1 is 60 in, rated drop 0.27 in. w.g.; Candidate 2 is 36 in/.25 and Candidate 3 is 84 in/.30. Constructed project: 36×24×84 in envelope, remaining drop budget 0.28 in. w.g., 3 dB upstream/5 dB downstream losses, 10000 ft³ furnished room and 5 ft receiver, independent 30 dB background and illustrative band budgets.
Calculation: At 63 Hz for Candidate 1: source 80 dB − upstream 3 dB − IL 6 dB = transmitted 71 dB Lw. Generated Lw 53 dB, with zero area adjustment, combines energetically to 71.068 dB. The Schultz receiver transfer is −7.388 dB; after 5 dB downstream loss, the path gives 58.681 dB Lp. Adding independent 30 dB background gives 58.686 dB. Against 60 dB budget, margin=1.314 dB and required IL accounting for fixed floors=4.667 dB.
Result: Candidate 1 meets all entered eight-band, envelope and pressure criteria. The 36 in candidate exceeds the 63 Hz budget; the 84 in candidate exceeds the remaining pressure allowance. Product coordinates are source data; project loads, paths, receiver and budgets are constructed. Historical shaded velocity/pressure ranges carry source cautions for acoustically sensitive applications; this is not a recommendation or actual field guarantee.