Duct sizing and geometry

Plan duct transitions and offsets from clear dimensions

Separate centered rectangular transitions, offset end planes, and two-elbow offsets, then carry the selected geometry into a fabrication and pressure review.

Three geometry tasks that should stay separate

A centered rectangular transition changes width and/or height while keeping the end centers aligned. An offset rectangular transition changes the end center position and evaluates four signed wall displacements. A two-elbow offset uses actual bend radii, tangent tails, a middle gap, and a connector cut allowance to move a constant-section duct and return the outlet parallel to the inlet.

The related calculators use different input contracts and formulas. Do not use the centered transition length as a two-elbow cut length, or use a single resultant offset as if it described every rectangular wall. Each result is geometric and preliminary; it does not provide pressure coefficients, seam allowances, or fabrication approval.

Three panels compare a centered rectangular transition, an offset rectangular transition with four signed wall displacements, and a two-elbow parallel offset with radii, tails and a straight gap.
Select the geometry model that matches the actual assembly before entering dimensions.
Match the task to the implemented calculator.
TaskRequired geometryPrimary result
Centered transitionStart/end clear width and height, selected per-wall angleMinimum axial length or wall-angle check
Offset rectangular transitionStart/end clear dimensions, signed X/Y center offsets, per-wall angleFour signed/absolute wall angles and controlling length
Two-elbow offsetEqual bend angle, radii, tangent tails, gap or resultant rise/overCut length, axial run, centerline offset, developed length

Use the rectangular transition modes

Enter start and end clear inside width and height in inches and a selected maximum wall angle measured from the original duct axis. The centered minimum-length mode splits each size change across two walls and uses the larger half-change as the controlling displacement. The available-length check calculates both width-side and height-side wall angles; the included angle is not the same criterion.

For an offset transition, confirm parallel end planes, fixed untwisted axes, signed center offsets, and a per-wall angle criterion. Positive X is right and positive Y is up in the documented end view. The calculator evaluates left, right, bottom, and top signed displacements separately. A zero included angle can coexist with a wall-angle failure when parallel offset walls are both tilted from the original axis.

The result is a geometric projection. It does not calculate area change pressure recovery, fitting loss, a flat pattern, seam allowance, panel cutting layout, installed outside clearance, or current code compliance.

Centered transition: Lmin = max(|W₂−W₁|/2, |H₂−H₁|/2) / tan(α) Offset wall displacements: Left/right = X ∓ (W₂−W₁)/2 Bottom/top = Y ∓ (H₂−H₁)/2 Wall angle = atan(displacement/L)

Input meaning for the offset transition model.
InputMeaningBoundary
Start/end dimensionsClear inside rectangular openingsNo sheet, liner, or outside envelope correction is inferred
X/Y center offsetsSigned end-center movementFixed view and parallel end-plane basis
Maximum wall anglePer-wall tilt from original axisNot an included angle or universal standard
Available lengthAxial separation of end planesNot sloping center-to-center distance

Independent offset-transition example

Use start 16 × 12 in, end 10 × 8 in, signed center offsets X = +3 in and Y = −2 in, and a 15° per-wall limit. The half-width change is (10−16)/2 = −3 in and the half-height change is (8−12)/2 = −2 in. The four signed wall displacements are left 3−(−3)=6 in, right 3+(−3)=0 in, bottom −2−(−2)=0 in, and top −2+(−2)=−4 in.

The largest absolute displacement is 6 in, so minimum axial length is 6/tan(15°) = 22.3923 in. At that length, the left wall is 15°, the top wall is about 10.1281°, and the right and bottom walls are 0°. The calculator returns the same controlling length and individual wall-angle results. A 24 in available length therefore leaves 1.6077 in axial margin in this constructed case.

Left = 3 − (10−16)/2 = 6 in Right = 3 + (10−16)/2 = 0 in Bottom = −2 − (8−12)/2 = 0 in Top = −2 + (8−12)/2 = −4 in Lmin = 6/tan(15°) = 22.3923 in

Independent four-wall projection.
WallSigned displacementAngle at Lmin
Left6 in15.0000°
Right0 in0.0000°
Bottom0 in0.0000°
Top−4 in−10.1281°
Controlling minimum length6/tan(15°)22.3923 in

Independent two-elbow offset example

Use two opposing 90° elbows with 6 in centerline radius each, inward diagonal tangent tails totaling 2 in, outer parallel tails totaling 3 in, total straight-piece insertion allowance 1 in, and required centerline offset 20 in. The two arcs contribute R(1−cosθ) = (6+6)(1−0) = 12 in of offset. The remaining diagonal centerline displacement is 20−12 = 8 in; after subtracting the 2 in inward tails, the installed straight gap is 6 in.

The straight-piece cut length is gap + insertion allowance = 6+1 = 7 in. In the existing 90° model, the axial end-to-end run is 15 in: the two arc projections contribute 12 in and the outer parallel tails contribute 3 in; the inward diagonal tails contribute to the offset construction and do not add an additional axial projection at 90°. Use the calculator’s stated geometry contract rather than replacing it with a generic triangle.

For the same inputs, the documented result is 7 in straight-piece cut, 20 in centerline offset, 15 in axial end-to-end run, and 29.8496 in developed centerline length. This is a fitting-drawing arithmetic example; confirm actual radii, tangent tails, connector engagement, and shop orientation before cutting.

Offset O = R(1−cosθ) + (G+B)sinθ Cut length = G + insertion allowance For the constructed 90° case: O = 12 + (6+2) = 20 in; cut = 6+1 = 7 in

Constructed two-elbow example retained by the calculator.
OutputIndependent basisCalculator display
Centerline offset12 + 6 + 220 in
Installed straight gap20 − 12 − 26 in
Straight-piece cut6 + 1 insertion allowance7 in
Axial runExisting 90° arc/tail projection model15 in
Developed centerline lengthArc + gap + tails29.8496 in

Move the geometry into the next review

Transfer the selected clear dimensions and offsets to the actual drawing. Check connection planes, liner, insulation, supports, access, turning clearance, and whether the chosen angle criterion applies to the fabrication standard. For a two-elbow offset, verify each fitting’s centerline radius, tangent tails, seam orientation, connector engagement, and whether the rise/over coordinate view matches the shop drawing.

Then evaluate airflow area and velocity change, fitting and transition pressure loss, acoustic consequences, and the complete critical path separately. A correct geometric layout can still fail an installation envelope or pressure budget.

Checks after the geometric result.
CheckQuestion
GeometryDo the clear end dimensions and signed offsets match the drawing?
FabricationAre radii, tangent tails, seams, connector engagement, and cut allowances documented?
InstallationDoes the outside assembly fit with insulation, supports, and access?
PerformanceAre area/velocity change and pressure loss included in the system model?

FAQs

Is a centered transition length a fabrication cut length? No. It is the minimum axial separation from the selected per-wall angle criterion.

Does rise/over direction rotate the rectangular end opening? No. It describes signed transverse movement in a fixed coordinate drawing; it is not connector clocking or section rotation.

Can the two-elbow result be used without the fitting drawing? No. Actual radii, tangent tails, insertion allowance, and equal-opposing-bend assumptions are required.

Conclusion and limits

Choose the centered transition, offset transition, or two-elbow model that matches the physical assembly. Keep clear geometry, signed offsets, per-wall angle, bend dimensions, and connector allowances visible, then carry the result into fabrication, installation, and pressure checks.

The calculator outputs are geometry models under their stated assumptions. They do not provide a shop drawing, universal angle limit, fitting pressure coefficient, seam allowance, structural check, or code approval.

Related calculators